Refrigerant Leak Diagnosed Mid-Season in WaterColor Vacation Rental

An AC that wasn't cooling in a WaterColor rental turned out to be more than a low-charge situation. A coil leak, three years of incremental underperformance, and a repair decision that actually made sense.

UpdatedJul 10, 2026 TypeLocal work Page131
Project type Local work
Location WaterColor
Scope Field-proven HVAC
Proof Local work
Updated Jul 10, 2026

The call came in at 8:40am on a Tuesday in late July. A WaterColor vacation rental, guests in the property, thermostat reading 81°F with the AC running. The property manager needed a tech on-site before checkout at 10am.

We were there by 9:20am.

What the diagnostic found

The outdoor unit was running. The indoor air handler was running. Airflow at the supply registers was normal. Suction line at the outdoor unit was warm — not cold, which it should be when refrigerant is boiling correctly in the evaporator coil. Refrigerant charge was down by approximately two and a half pounds on a system spec'd to hold eight pounds.

A system doesn't lose refrigerant through normal operation. Refrigerant is a closed loop. What it loses through is a leak — usually at a fitting, a coil joint, or a corroded line-set connection. We traced it to a pinhole leak at the evaporator coil header — formicary corrosion accelerated by years of coastal salt-air exposure at the coil face.

The system was nine years old. On a system that age in good condition otherwise, evaporator coil replacement makes sense. On a system much older, the math tilts toward full replacement. This one was repairable.

The repair

We recovered the remaining refrigerant, replaced the evaporator coil with a TXV-equipped replacement coil matched to the existing air handler, pressure-tested the system to 410 PSI with nitrogen for 30 minutes with no drop, pulled vacuum, and recharged to manufacturer-spec. Total time on-site: four hours.

Guests were able to stay. The system reached setpoint within an hour of the recharge. Checkout proceeded normally.

The property manager was on-site for walkthrough at 1:30pm and confirmed everything was operating before the next guests arrived.

Refrigerant leaks don't announce themselves until the system can't keep up. If your 30A rental's energy bills have crept up over the past two or three summers without explanation, a refrigerant charge check during a maintenance visit is a reasonable first look. Maintenance plans here.

Licensed & Insured (CAC1823754) NATE-Certified Licensed since 2014
Call +1-850-502-9872 — or fill out the form below.
Urgent? Call for the fastest response. Not sure? Send what you know. Next step: We confirm before scheduling.
For a faster call back

Property Location (add more if you have several)

Property 1
Service(s) needed (select all that apply)

Optional. Attach up to 8 files, 12 megabytes each. Up to 8 files · 12 MB each · JPG · PNG · HEIC · MP4 · MOV · PDF

    By submitting this form you agree to our Privacy Policy. We never sell your information.